The failure rates of components used in the calculation process of
related safety parameters mentioned above are based on the Sie-
mens database: SIEMENS NORM SN_29500.
The PFH value is less than 2% of the total failure budget of a SIL3
safety loop.
"Mission Time" and "Proof Test Interval":
The "Mission Time" of all components used must be observed
and complied with. After the "Mission Time" of a component
has elapsed, the component must be discarded or replaced. It
is not allowed to continue operating the component!
After the component was discarded ("Mission Time" has
elapsed), it must be ensured that it cannot be reused (e.g., by
disabling it).
There is no specified "Proof Test Interval" for the drive system.
Therefore, the "Mission Time" cannot be reset by a "Proof Test
Interval".
The safety function operates in High Demand Mode, where the
safety function is only performed on demand, in order to transfer
the EUC into a specified safe state, and where the frequency of
demands is greater than one per year.
EFC x610 Series Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-X610***-IT05-EN-P
387/389

Table of Contents

Other manuals for REXROTH EFC 3610 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REXROTH EFC 3610 Series and is the answer not in the manual?

REXROTH EFC 3610 Series Specifications

General IconGeneral
BrandREXROTH
ModelEFC 3610 Series
CategoryDC Drives
LanguageEnglish

Related product manuals