16
Engineer programming via the keypad
Timers
114
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
RETRIGGER DURESS
ENABLED/DISABLED
RETRIGGER PANIC
ENABLED/DISABLED
SILENCE AUD VER.
ENABLED/DISABLED
ENGINEER EXIT
ENABLED/DISABLED
* Not available for SPC42xx, SPC43xx.
16.3 Timers
1. Scroll to TIMERS and press SELECT.
2. Scroll to the desired programming option:
Timers
Designation of the functions in the following order:
1
st
row: Web/SPC Pro
2
nd
row: Keypad
Timer
Description
Default
Audible
Internal Bells
INT BELL TIME
Duration that internal sounders will sound when alarm is
activated. (1 15 minutes: 0 = never))
15 min.
External Bells
EXT BELL TIME
Duration that external sounders will sound when alarm is
activated. (1 15 minutes; 0 = never)
15 min.
External Bell Delay
EXT BELL DELAY
This will cause a delayed activation of the external bell. (0
600 seconds)
0 sec.
Chime
CHIME TIME
Number of seconds that a chime output will activate, when a
zone with chime attribute opens. (1 10 seconds)
2 sec.
Confirmation
Confirm
CONFIRM TIME
Note: Only available when Security Grade is
‘Unrestricted’ and ‘DD243’ is selected for ‘Confirmation’
variable. (See System Options [➙ 222])
This timer applies to the alarm confirmation feature and is
defined as the maximum time between alarms from two
different non overlapping zones that will cause a confirmed
alarm. (30 60 minutes)
30 min.
Confirmed holdup
This timer applies to the confirmed holdup feature and is
defined as the maximum time between alarms from two
different non-overlapping zones that will cause a confirmed
alarm. (480 - 1200 minutes)
480 min.
Dialer Delay
DIALER DELAY
When programmed, the dialler delay initiates a predefined
delay period (0 -30 seconds) before the system dials out to an
Alarm Receiving Centre (ARC). This is specifically designed
to reduce unwarranted responses from Alarm Receiving
Centres and the constabulary. In the event of a subsequent
zone being tripped the dialler delay period is ignored and the
dialler dials out immediately. (0 30 seconds)
30 sec.
Alarm abort
ALARM ABORT
Time after a reported alarm in which an alarm abort message
can be reported. (0 999 seconds))
30 sec.
Setting
Setting Authorisation
SETTING AUTH
Period for which Setting Authorisation is valid. Enter a value
between 10 and 250 seconds.
20 secs
Final Exit
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute
7 sec.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vanderbilt SPC53 Series and is the answer not in the manual?

Vanderbilt SPC53 Series Specifications

General IconGeneral
BrandVanderbilt
ModelSPC53 Series
CategoryPower Supply
LanguageEnglish

Related product manuals