Engineer programming via the keypad
Installation & Configuration Manual
* Not available for SPC42xx, SPC43xx.
16.3 Timers
1. Scroll to TIMERS and press SELECT.
2. Scroll to the desired programming option:
Timers
Designation of the functions in the following order:
1
st
row: Web/SPC Pro
2
nd
row: Keypad
Duration that internal sounders will sound when alarm is
activated. (1 – 15 minutes: 0 = never))
Duration that external sounders will sound when alarm is
activated. (1 – 15 minutes; 0 = never)
This will cause a delayed activation of the external bell. (0 –
600 seconds)
Number of seconds that a chime output will activate, when a
zone with chime attribute opens. (1 – 10 seconds)
Note: Only available when Security Grade is
‘Unrestricted’ and ‘DD243’ is selected for ‘Confirmation’
variable. (See System Options [➙ 222])
This timer applies to the alarm confirmation feature and is
defined as the maximum time between alarms from two
different non overlapping zones that will cause a confirmed
alarm. (30 – 60 minutes)
This timer applies to the confirmed holdup feature and is
defined as the maximum time between alarms from two
different non-overlapping zones that will cause a confirmed
alarm. (480 - 1200 minutes)
When programmed, the dialler delay initiates a predefined
delay period (0 -30 seconds) before the system dials out to an
Alarm Receiving Centre (ARC). This is specifically designed
to reduce unwarranted responses from Alarm Receiving
Centres and the constabulary. In the event of a subsequent
zone being tripped the dialler delay period is ignored and the
dialler dials out immediately. (0 – 30 seconds)
Time after a reported alarm in which an alarm abort message
can be reported. (0 – 999 seconds))
Period for which Setting Authorisation is valid. Enter a value
between 10 and 250 seconds.
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute