Installation & Configuration Manual
Hardware Requirements
The back tamper kit (SPCY130) must be installed for panels and power
supplies for compliance with EN50131 Grade 3.
EN50131 Grade 3 compliant components must be installed for EN50131 Grade
3 compliant systems.
Either EN50131Grade 2 or 3 compliant components must be installed for
EN50131 Grade 2 compliant systems.
It is not possible to enrol a wireless device with a signal strength lower than 3.
The recommended ratio of wireless receivers to transmistters is no more than
20 transmitters for every one receiver.
Glassbreak must be used with an EN-compliant glassbreak interface.
To comply with EN50131-3:2009, do not set or unset the system using the
SPCE120 (Indicator Expander) or the SPCE110 (Keyswitch Expander).
The SPCN110 PSTN module and SPCN130 GSM/GPRS module are tested with
EN50131 approved Grade 2 and Grade 3 panels and can be used with these
approved panels.
3.1.3 Compliance with EN 50136-1:2012 and EN 50136-2:2014
SPC products listed have been tested according to EN 50136-1:2012 and EN
50136-2:2014.
3.1.4 Compliance with INCERT Approvals
Software Requirements
Selecting Belgium (*) under Region implements local or national requirements
which supercede EN50131 requirements.