Installation & Configuration Manual
Compliance by SPC using third party ARC software. Indication external to the
building must be provided by means of a timed buzzer/strobe, etc. that will operate
on a system unset for a timed period e.g. 30 seconds.
Refer to the following sections in this manual:
Timers [âž™ 114]
3.1.5.4 Configuration requirements for PD 6662:2010
conformance
Recommendations for the recording of remotely notified alarm
conditions (BS 8243:2010 - Annex G.1 and G.2
Alarm conditions can be categorised for analysis in accordance with Annex G if the
SPC system is configured so that the entry timer is less than 30 seconds, and the
dialer delay is set to 30 seconds.
Refer to the following sections in this manual:
AREAS [âž™ 116]
Adding / Editing an area [âž™ 238]
Timers [âž™ 114]
Requirements for systems using dedicated alarm paths (BS EN
50136-1-2, 1998
The SPC system should be configured to do an automated test call to the ARC.
The SPC system should be configured with a 'Fail to Communicate‘ output.
Refer to the following section in this manual:
Adding/Editing an ARC [âž™ 292]
Requirements for equipment used in systems with digital
communicators using PSTN (BS EN 50136-2-2, 1998)
Fault Output
The SPC system should be configured with a 'Fail to Communicate‘ output.
Refer to the following sections in this manual:
OUPUTS [âž™ 136] (Keypad)
Configuring controller inputs & outputs [âž™ 196] (Browser)
Adding/Editing an ARC [âž™ 292]
Retransmission Attempts
Retransmission attempts (Dial Attempts) are configured in this manual:
Adding/Editing an ARC [âž™ 292]
Editing EDP settings [âž™ 301]
A minimum of 1 and a maximum of 12 retransmissions are allowed.
Intrusion and hold-up - System design (DD CLC TS 50131-7, 2008
Setting and unsetting
SPC system is configurable in such a way that the setting is completed by 'Final
Exit'.
It is possible to configure the SPC so that a WD (Warning Device) is activated
momentarily on setting.