Disabled: If a non-entry/exit zone is activated during the
exit timer countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted
grade is selected as enabling it is not in accordance with
EN50131. When you choose the Swiss or Belgium
Region under Standard Compliance Settings, this option
is automatically enabled but it is not visible under
Options.
Disabled: If a non-entry/exit zone is activated during the
entry timer countdown, an alarm is not raised.
Note: This option only displays when the Unrestricted
grade is selected as enabling it is not in accordance with
EN50131. When you choose the Swiss Region under
Standard Compliance Settings, this option is
automatically enabled but it is not visible under Options.
BS8243:
This will enforce compliance with the UK Police
requirements, and is a specific requirement for UK
Commercial installations. The requirement stipulates
that an alarm will only be deemed to be a confirmed
alarm if it meets the following condition:
After an initial zone alarm has been activated and
before the alarm confirmation time has expired, a
second zone alarm is activated. The alarm
confirmation time must be between 30 and 60
minutes. (See Timers [➙ 230])
If a second zone alarm is not activated within the
Alarm confirmation time, then the first zone alarm will
be inhibited. The BS8243 confirmation option is
automatically set whenever the Standards -> Region
option is set to UK.
Garda:
This will enforce the policies for confirmed alarms
required by the Irish Garda. The requirement
stipulates that an alarm will be deemed to be a
confirmed alarm as soon as a second zone alarm is
activated on the system within the one alarm set
period. The Garda confirmation option is
automatically set whenever the Standards -> Region
option is set to Ireland.
EN-50131-9
This will enforce compliance with the EN-50131-9
standard and the Spanish “INT/316/2011 Order of 1
February on the operation of alarm systems in the
field of private security”. This requirement stipulates
that an alarm will only be deemed to be a confirmed
alarm if it meets the following conditions:
- 3 zone activations in 30 minutes (default), whereby