17
Engineer programming via the browser
Configuration
232
Vanderbilt
Installation & Configuration Manual
A6V10276959
01.05.2016
Timer
Description
Default
Mains Delay
MAINS SIG DELAY
The time after a mains fault has been detected before an alert
is activated by the system. (0 – 60 minutes)
0 min.
Engineer
Engineer Access
ENGINEER ACCESS
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0 – 999 minutes. ‘0’ indicates
no time limitation for system access)
0 min.
Engineer auto log out
ENG AUTO LOG OUT
Duration of inactivity after which the engineer will be
automatically locked out
0 mins.
Keypad
Keypad Timeout
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10 – 300 seconds)
30 sec.
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default ( 0 - 9999 seconds; 0 = never).
10 secs
Fire
Fire Pre-alarm
FIRE PRE-ALARM
Number of seconds to wait before reporting fire alarm for
zones with ‘Fire pre-alarm’ attribute set. (1 – 999 seconds)
See Editing a Zone [âž™ 237].
30 sec.
Fire recognition
FIRE RECOGNITION
Extra time to wait before reporting file alarm for zones with
‘Fire pre-alarm’ and ‘Fire Recognition’ attributes set. (1 – 999
seconds). See Editing a Zone [âž™ 237].
120 sec.
PIN
PIN Valid
PIN VALID
Period for which pin is valid in days ( 1 - 330 )
30 days
PIN Changes Limit
PIN CHANGES LIMIT
Number of changes within a valid period ( 1 - 50 )
5
PIN Warning
PIN WARN
Time before PIN expiry after which a warning will be
displayed
( 1 - 14 )
5 days
General Settings
RF Output Time
RF OUTPUT
The time that the RF output will remain active on the system.
(0 – 999 seconds)
0 sec.
Time Sync Limit
TIME SYNC LIMIT
Time limit within which no event will be reported.
(0 – 999 secs) Time synchronization only takes place if
system time and update time are outside this limit.
0 sec.
Link Timeout
LINK TIMEOUT
Timeout for Ethernet link fault (0 = Disabled) ( 0 - 250 )
0 secs
Camera Offline
CAMERA OFFLINE
Time for camera to go offline ( 10 - 9999 )
10 secs
Tech. delay
TECH. DELAY
Number of seconds to delay triggering of tech. zones with
tech. delay attribute. (0 – 9999 seconds)
0 sec.
Frequent
FREQUENT
This attribute only applies to Remote Maintenance. The
number of hours a zone must open within if the zone is
programmed with the Frequent use attribute. (1 – 9999 hours)
336 hours (2
weeks)
Duress silent
Time when duress will remain silent and not restorable from
keypad (0 - 999).
0 Minutes
Holdup/panic silent
Number of minutes that a holdup/panic will remain silent and
cannot be restored from the keypad (0 - 999).
0 Minutes
!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vanderbilt SPC53 Series and is the answer not in the manual?

Vanderbilt SPC53 Series Specifications

General IconGeneral
BrandVanderbilt
ModelSPC53 Series
CategoryPower Supply
LanguageEnglish

Related product manuals