Engineer programming via the browser
Installation & Configuration Manual
The time after a mains fault has been detected before an alert
is activated by the system. (0 – 60 minutes)
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0 – 999 minutes. ‘0’ indicates
no time limitation for system access)
Duration of inactivity after which the engineer will be
automatically locked out
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10 – 300 seconds)
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default ( 0 - 9999 seconds; 0 = never).
Number of seconds to wait before reporting fire alarm for
zones with ‘Fire pre-alarm’ attribute set. (1 – 999 seconds)
See Editing a Zone [âž™ 237].
Extra time to wait before reporting file alarm for zones with
‘Fire pre-alarm’ and ‘Fire Recognition’ attributes set. (1 – 999
seconds). See Editing a Zone [âž™ 237].
Period for which pin is valid in days ( 1 - 330 )
Number of changes within a valid period ( 1 - 50 )
Time before PIN expiry after which a warning will be
displayed
The time that the RF output will remain active on the system.
(0 – 999 seconds)
Time limit within which no event will be reported.
(0 – 999 secs) Time synchronization only takes place if
system time and update time are outside this limit.
Timeout for Ethernet link fault (0 = Disabled) ( 0 - 250 )
Camera Offline
CAMERA OFFLINE
Time for camera to go offline ( 10 - 9999 )
Number of seconds to delay triggering of tech. zones with
tech. delay attribute. (0 – 9999 seconds)
This attribute only applies to Remote Maintenance. The
number of hours a zone must open within if the zone is
programmed with the Frequent use attribute. (1 – 9999 hours)
Time when duress will remain silent and not restorable from
keypad (0 - 999).
Number of minutes that a holdup/panic will remain silent and
cannot be restored from the keypad (0 - 999).