TLS-450 Setup and Operation Screens Manual
93
Volume
New Chart - This field is blank - You enter the tank chart value or the metered volume dispensed or
dropped for this point. Edit Chart - Displays the volume entered for this point. Allowable range: 0 to
264,172 gal (0 to 999,999 Litres)
Edit Point
Touch this button to open the 'Add/Edit Tank Chart Point' dialog box for the selected
point (see Add Point button above).
Delete Point
Touch this button to remove a selected point from a chart.
Make Chart
This button is grayed out until at least 10 points have been entered for a new chart. Touch this button to
create a chart from the entered points.
Setup
Touch this button to open the 'Tank Chart Setup' dialog box described below:
Function
Allowable Selections: Create New Chart, Update Non-Active Chart, or View Chart. Default: Create New
Chart.
Chart Name
Enter a name for the chart you want to created or for the tank chart you want to view or update.
New Chart
Allowable Selection: 1 to 20 alphanumeric characters. Default: Blank
Existing Chart
Select from a drop down list of previously created charts
Source
Enter the source of chart points for the chart.
Allowable Selections: User Entered, Metered Drop, Metered Dispense. Default: User Entered
Volume Entry
Grayed out except for User Entered calibration.
Allowable selections: Total Volume (meter totalizes dispensed amounts) or Volume Change (meter reads
dispensed amount). Default: Total Volume
Max. Step
This is a read only field showing the volume of the tank at 5% of its capacity. It is recommended that this
difference in dropped or dispensed volume not be exceeded between points.