TLS-450 Setup and Operation Screens Manual
304
• Communication Alarm
• Fault Alarm
• Install Alarm
Serial Number
Sensor Serial Number
Value: XXXXXXX
Date
Sensor Date Code
Value: Year/week (YY/WW)
Fuel Height
Fuel Height detected by the Mag Sensor
Value range: 0.00 to 48.00 in. (0.00 to 1219.20mm)
Water Height
Water Height detected by the Mag Sensor
Value range: 0.00 to 48.00 in. (0.00 to 1219.20mm)
Total Height
Absolute liquid height as measured by the Mag Sensor
Value range: 0.00 to 48.00 in. (0.00 to 1219.20mm)
Fluid Temp
Temperature of the fluid in which the Mag Sensor is submerged
Value range: -40.0 to 140.0°F (-40.0 to 60.0°C)
Brd Temp
Temperature of the Mag Sensor's printed circuit board
Value range: -40.0 to 140.0°F (-40.0 to 60.0°C)
Mag Sensor Diagnostics - General Screen Refresh Rate
The Mag Sensor Diagnostics - General data will be refreshed every 8 seconds.
Control Button (right of screen)
Setup
Touch this button open the Device Setup - Mag Sensor
screen.