TLS-450 Setup and Operation Screens Manual
126
Reconciliation
Reconciliation Setup - General
This screen lets you setup general Reconciliation parameters.
Product Threshold Alarm
If enabled, the Product Threshold Alarm will be activated when the programmed threshold for
discrepancies between the fuel delivered amount and the dispensed fuel amount is exceeded. The
system default is 1.00% of total meter sales (throughput) plus 130 gallons (492 litres) offset. In the U.S.
the EPA has set this default as a criteria not to be exceeded. The Product Threshold Alarm is triggered
when the Alarm Threshold plus offset exceeds the allowed variance.
Allowable selections: Enabled, Disabled
Default: Disabled
Daily Close Time
Enter the time you wish to designate as the daily closing time. At the programmed time, the system stores
the current day's data, and prints a report. This feature cannot be disabled.
Allowable Selections:
• Hour: 0 to 23 (1 to 12 if 12 hour format)