TLS-450 Setup and Operation Screens Manual
196
Mass
This column will not display if the probe does not measure density.
Allowable range: Depends on tank volume and fuel density
Fuel Density
This column will not display if the probe does not measure density.
Allowable range: 42.139 to 56.185 lbs/ft
3
(675.00 to 900.00 kg/m
3
)
Fuel TC Density
This column will not display if the probe does not measure density and if TC density is not enabled.
Allowable range: 42.139 to 56.185 lbs/ft
3
(675.00 to 900.00 kg/m
3
)
Ullage 100%
Allowable range: 0 to 264,172 gal (0 to 999,999L)
Ullage xx%
The User defined ullage is only displayed if defined in 'All Tank' setup.
Allowable range: 0 to 264,172 gal (0 to 999,999L)
Fuel Height
Allowable range: 0 to 390.0 in. (0 to 9906.0mm)
Water Height
This column will be blank if the probe does not measure water.
Allowable range: 0 to 390.0 in. (0 to 9906.0mm)
Water Volume
This column will be blank if the probe does not measure water.
Allowable range: 0 to 264,172 gal (0 to 999,999L)
Fuel Temp.
This column will be blank if the probe does not measure temperature.
Allowable range: -40.0 to 140.0°F (-40.0 to 60.0°C)
Current Inventory Report Screen Refresh Rate
The current inventory data will be refreshed every 30 seconds.

Table of Contents