TLS-450 Setup and Operation Screens Manual
276
Report Column Descriptions
Date & Time
Time the reconciliation record was added.
Metered Sales
The total metered sales over the defined reconciliation period.
Variance
Total variance over the defined reconciliation period.
Reasons
Possible messages:
DIM out/alarm/setup issues - Any dim alarms. All tanks will be set.
DIM missing starts or stops - Set when a fake start or fake end event is generated. A fake start
indicates we received an end event but no start event. A fake end indicates we have received a
start event and no event. Normal trigger time is 15 minutes. All tanks will be set.
DIM data from phantom meters - When an 'invalid meter' (end event and meter count = 0 or > 2)
is received All tanks will be set.
Meter-map - not complete - Set when any dim events received and one of the tanks is not
mapped. All tanks will be set.
Meter-map - unstable/changes during period - Any time the meter map table is changed (reset,
clear, unlock, lock, mapped). All tanks will be set.
Invalid fuel height - When an 'Invalid Fuel Height' is triggered. Set per individual tank.
Probe out - When a 'Probe Out Alarm' is triggered. Set per individual tank.
Water removed - Check at Daily /Shift close time. Set when the water height from the previous
close is greater then the current water height. Set per individual tank.
Power outage - Always get set on power up or system reset. All tanks will be set.
Tank Chart Change (indicate what tank chart is used, and its quality level) [set per tank] - Check
at Daily /Shift close time.
Set when the time of the tank chart from the previous close is different from the current recorded
time. Set per individual tank.
DIM Queue Overrun - When we are receiving more Dim events then can be handled. All tanks
will be set.