TLS-450 Setup and Operation Screens Manual
213
Report Column Descriptions
Start/End Date & Time
Allowable range: 01/01/2005 to 12/31/2038 (MMDDYYYYY) 00:00 to 23:59 (HH:MM)
Fuel Volume
Allowable range: 0 to 264,172 gal (0 to 999,999L)
Fuel TC Volume
The Fuel TC Volume column will not be displayed unless the Print TC Volume feature is enabled in
System Setup and the probe measures temperature.
Allowable range: 0 to 264,172 gal (0 to 999,999L)
Mass
This column will not display if the probe does not measure density.
Allowable range: Depends on tank volume and fuel density
Fuel Density
This column will not display if the probe does not measure density.
Allowable range: 42.139 to 56.185 lbs/ft
3
(675.00 to 900.00 kg/m
3
)
Fuel TC Density
This column will not display if the probe does not measure density and if TC density is not enabled.
Allowable range: 42.139 to 56.185 lbs/ft
3
(675.00 to 900.00 kg/m
3
)
Water Height
This column will be blank if the probe does not measure water.
Allowable range: 0 to 390.0 in. (0 to 9906.0mm)
Fuel Temp.
This column will be blank if the probe does not measure temperature.
Allowable range: -40.0 to 140.0°F (-40.0 to 60.0°C)
Fuel Height
Allowable range: 0 to 390.0 in. (0 to 9906.0mm)