TLS-450 Setup and Operation Screens Manual
202
Report Column Descriptions
Test Type
Possible messages:
• Fullest Annual
• Fullest Periodic
• Last Annual
• Last Gross
• Last Periodic
Date & Time
Date and time of test.
Test Method
Possible messages:
• SLD
• CSLD
Total Hours
The Total Hours field will always be blank for a gross test. Gross tests run for 30 minutes maximum; the
duration is not configurable or reported.
Possible length of test: 0 to 24
Average Volume
Allowable range: 0 to 264,172 gal (0 to 999,999L)
% Volume
Allowable range: 0.0 to 100.0%
Control Buttons (on right of screen)
Tank Test Setup
Touch this button open the Tank Setup – Environmental Test screen.
Regulatory Compliance
Note: In-tank leak tests will not be declared a PASS unless the product level in the tank satisfies the
minimum product level defined in our Third Party certification for the leak test being performed. In-tank
leak tests performed with the product level below these minimum levels will be declared Invalid. Because
the minimum product level requirements vary with local, state, and federal regulations, you need to
ensure that the product level complies with the applicable regulations in your location.

Table of Contents

Other manuals for Veeder-Root TLS-450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450 and is the answer not in the manual?

Veeder-Root TLS-450 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450
CategoryMusic Mixer
LanguageEnglish

Related product manuals