TLS-450 Setup and Operation Screens Manual
236
Tank Test Diagnostics - CSLD Rate Table
The CSLD Rate Table diagnostic report lists detailed data for the last 30 days of CSLD leak tests. A
maximum of 80 of the most recent tests are stored in the rate table. The default view is 30 days of data
for all tanks.
Siphon manifolded tanks are treated as one tank in CSLD. The tanks in the manifolded set share the
same table and results. Deleting the table for any tank within the set will in effect delete the table of all the
members in the set.
You will only be able to access tanks that have CSLD enabled or have CSLD history.
Report Column Descriptions
Date/Time
Value range: Date and Time
Status
0 = Test valid
1 = Test rejected - duration too short
2 = Test rejected - start time too close to a delivery
3 = Test rejected - excessive dispensing prior to test