TLS-450 Setup and Operation Screens Manual
247
Test Rate
Allowable selections: 0.1 gal/hr (0.38 ltr/hr), 0.2 gal/hr (0.76 ltr/hr)
Default: 0.2 gal/hr
Test Duration
The Test Duration field will be present only when the Test Control is set to Timed Duration.
Allowable selections: 2 - 24 hours
Default: 2 hours
Test Control Buttons (on right of screen)
Start
Touch this button to start a manual test of a selected tank. This button is disabled if tests are running for
the currently selected tank, or if Start All Tanks is selected to start tests for all tanks.
Stop
Touch this button to stop a manual test of a selected tank. This button is disabled if test are not running
for the currently selected tank, or if Stop All Tanks is selected to stop tests for all tanks.
Start All Tanks
Touch this button to start an SLD test for all tanks using the field selections for an individual tank.
Stop All Tanks
Touch this button to stop all SLD tests that are running.