128
Reconciliation Setup - Threshold Alarms
This screen contains information that allows you to select up to four reconciliation compliance monitoring
test protocols.
You select one or more threshold determining references for each test protocol. The reference selections
are: throughput, tank capacity, deliveries, or a fixed value. You input percentage and offset values that
are applied to the reference selection to determine the threshold value. In the case of multiple references
the largest threshold value is used to determine the result. The threshold references are:
• Percentage of throughput + vol. offset
• Percentage of (tank) capacity + vol. offset
• Percentage of deliveries + vol. offset
• Fixed value
Test Type
Select the monitoring period for the selected test protocol.
• Monthly - The threshold is compared against the monthly variance summation over a calendar
month. The test is performed monthly.
• Rolling - You define the number of rolling days. The threshold is compared to the variance
summation over the defined number of days. The test is performed daily.
• Daily - The daily variance is compared to the threshold. The test is performed daily.

Table of Contents

Other manuals for Veeder-Root TLS-450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450 and is the answer not in the manual?

Veeder-Root TLS-450 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450
CategoryMusic Mixer
LanguageEnglish

Related product manuals