TLS-450 Setup and Operation Screens Manual
269
Tank/Blend
Possible messages:
• Tank Label
• Blend Label
• Unmapped
• Probeless (unmonitored tanks, such as propane)
• R (retired) - If an unmapped meter has not been reported by a POS within 24 hours of the last
report, the meter is declared 'retired'. A retired meter may be a phantom meter incorrectly
reported by the POS, or it may be a seldom heard from meter, such as one connected to a
kerosene tank. Until the 'retired' meter is mapped, every time the meter is activated, and for 24
hours thereafter, BIR is suspended.
Locked
User has locked tank-to-meter mapping for this meter. Auto meter mapping will not change it.
Last Report Time
Last transaction reported for this meter.
Control Buttons (Right side of screen)
Edit
This button is grayed out unless at least one record in the data view area is selected. When the desired
record is highlighted, touch the Edit button to display the 'Edit Tank Map' - dialog box which is described
below:
Edit Tank Map - Dialog Box
The selected record will populate the appropriate fields in the 'Edit Tank Map' dialog. When the 'Tank
Map' record has been edited using the 'Edit Tank Map' dialog, the new data will replace the old data in the
selected record. The fields of the Edit Tank Map dialog are described below:
• Locked - The user can only lock an entry if it is mapped or probeless. Retired entries are
unmapped, and cannot be locked. A Probeless tank assignment will be locked. You cannot
unlock the meter assignment (the Locked field is inactive). Touch the Down arrow to select: Yes
or No.
• Tank/Blend - Touch the Down arrow to select:
• Tank Label
• Blend Label
• Unmapped - Select this entry if the meter was incorrectly mapped and you want the automapping
feature to correctly map the meter (This suspends BIR until the meters are all mapped).
• Probeless - Select this entry for meters from which the POS reports activity, but that are not
monitored by the TLS, such as propane or kerosene.
• User FP - Touch the numeric keypad button to enter the desired fuel position. Allowable
selections: 1 to 72
• Real FP - This field is read only and the entry is based on the selected Map Record.
• Real Meter - This field is read only and the entry is based on the selected Map Record.