% of Deliveries
This Alarm Threshold is the discrepancy between the Fuel Delivery amount and the Variance amount
(Physical Inventory - Calculated Inventory).
The system default is 1.00% of total Fuel Delivery plus 130 gallons (492 litres) offset. In the U.S. the EPA
has set this default as a criteria not to be exceeded. Alarm Threshold must be between 0.00 and 9.99
percent.
Allowable selections: 0.00 to 9.99
Default: 1.00
Vol. Offset
Enter the offset amount to be added to the % of Deliveries value that will trigger the Product Threshold
Alarm.
Allowable selections: 0 to 264172 gal. (0 to 999,999 Litres)
Default: 130 gal. (492 Litres)
Fixed Value
This Alarm Threshold is the discrepancy between the Fixed Value and the Variance amount (Physical
Inventory - Calculated Inventory) without any offset.
Allowable selections: 0 to 264172 gal. (0 to 999,999 Litres)
Default: 80 gal (302 litres)