TLS-450 Setup and Operation Screens Manual
244
Test Type
Value range: 0.1 gal/hr Test (0.38 L/hr Test), 0.2 gal/hr. Test (0.76 L/hr Test)
Result
Possible messages:
Invalid
Pass
Fail (may be blank)
Reason
More than one reason may be displayed in a comma separated list. The reasons may change as the test
progresses.
The possible messages that will display in this column are:
Head Temp Chg (probe head temperature changed too much)
Insuf Smpl on First Per (insufficient TLS samples In first period)
Insuf Smpl on Last Per (insufficient TLS samples In last period)
Invalid Fuel Level (insufficient separation between fuel and water floats)
Percent Vol Too Low (tank volume too low)
Product Level Increase (leak rate is excessively positive)
Recent Delivery (test started too soon after delivery)
SLD Float size too small (fuel float diameter too small)
SLD Low Level Err (fuel Level too low to temperature compensate)
SLD Probe Incapable of Test (probe doesn't support test)
Temp Chg (average fuel temperature changed too much)
Temp out of Range (one or more in-fuel thermistors out of range)
Test too Short (test too short)
Zone Temp Chg (one or more in-fuel thermistors changed too much)
Start Time
Value range: Date/Time
Duration
Value range: 0 - 24 hours (blank for gross test)
Start Temp
Value range: -40.0 to 140.0°F (-40.0 to 60.0°C)
Leak Rate
Value range: -26.417 to 26.417 gal (-99.999 to 99.999L)
End Temp
Value range: -40.0 to 140.0°F (-40.0 to 60.0°C)