TLS-450 Setup and Operation Screens Manual
353
Dispenser Pan Sensor
(Solid-State)
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Verify sensor is firmly secured in an
upright position on the bottom of the
pan.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
Containment Sump
Sensor (Solid-State)
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Verify sensor is firmly secured in an
upright position on the bottom of the
containment sump.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
Vapor Sensor Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor cable if cracked or
Groundwater Sensor Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Lift sensor above water level in the
well and verify the system activates
a 'WATER OUT' alarm.
B. Service Contractor
1. Verify epoxy kits have been installed
on field wiring.
2. Replace sensor if cable is cracked
or damaged (ref. item A.1).
3. If the sensor does not alarm (ref.
item A.2), replace the sensor.
Hydrostatic Sensor Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
B. Service Contractor
1. Remove sensor from brine reservoir
and verify floats move freely. With