TLS-450 Setup and Operation Screens Manual
43
Serial Number (Read Only)
Probe Type (Read only)
Float Type
Enter the installed Mag probe float size. The console automatically recognizes which Mag probe type you
have installed and will display only the applicable float size options. Only select "Custom" if the literature
that was shipped with the float specifically states that you must choose this float size selection, i.e.,
Chem-ISO and LPG-ISO probes. The installation literature accompanying Chem-ISO and LPG-ISO
probes will list the required values to enter.
Allowable selections: Standard Mag Probe: 4 in. (101mm), 2 in. (50mm) and Custom. Low-Level Mag
Probe: 4 in. (101mm), 3 in. (76mm), 2 in. (50mm), 1 in. (25mm) and Custom. Low-Level Mag Probes -
MAG7, MAG8 and MAG9: 4 in. (101mm), 3 in. (76mm), 2 in. (50mm), 1 in. (25mm), 4 in. Phase
Separation and Custom.
Default: 2 in.(50mm), 3 in.(76mm) or 4 in. (101mm) depending on probe type.
Notes:
1. If the Custom float size is selected, fuel offset, invalid fuel, water offset, and water minimum
parameter fields below are enabled for edit.
2. Only circuit codes, D004, D005 and D006 are allowed to set the float type to 4 in phase
separation.
Fuel Offset (Custom Float Type)
Allowable selections: -8 in. to 8 in. (-203.2 to 203.2mm)
Default: Default varies according to Probe type and Float type. Refer to tables below for US
values. Metric values are calculated using the formula; mm = 25.4 * in.
Water Offset (Custom Float Type)
Allowable selections: -8 in. to 8 in. (-203.2 to 203.2mm)
Default: Default varies according to Probe type and Float type. Refer to tables below for US values.
Metric values are calculated using the formula; mm = 25.4 * in.
Water Min. (Custom Float Type)
Allowable selections: 0 to 10 in. (0 to 254mm)
Default: Default varies according to Probe type and Float type. Refer to tables below for US values.
Metric values are calculated using the formula; mm = 25.4 * in.
Invalid Fuel (Custom Float Type)
Note: The invalid fuel level assumes no water is present. If water is present, the invalid fuel level is
increased by the water level reading.
Allowable selections: 0 to 10 in. (0 to 254mm)
Default: Default varies according to Probe type and Float type. Refer to tables below for US values.
Metric values are calculated using the formula; mm = 25.4 * in.