TLS-450 Setup and Operation Screens Manual
46
• MOMENTARY - The On/Off state is determined by assigned alarms/warnings. However, relay
returns to the inactive state after the Alarm button is touched to acknowledge the alarm.
• PUMP COMM CONTROL - Select this relay type only when a set of line manifolded pumps are
using Red Jacket IQ Controllers, and you want to run PLLD precision line leak tests. After
selecting this relay type, when one IQ controlled pump of a manifolded set is turned On for line
leak testing, the relay will activate, blocking communication with the second IQ controlled pump
(giving the console total control of the pumps) until the precision test is complete.
Allowable selections:
• Standard
• Pump Control Output
• Momentary
• Pump Comm Control
Default: Standard
Orientation
You must identify the input switch orientation as either normally open or normally closed so the console
properly recognizes an ON or OFF condition.
Allowable selections: Normally Open, Normally Closed
Default: Normally Closed