EasyManuals Logo

Veeder-Root TLS-450 Setup And Operation

Veeder-Root TLS-450
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
TLS-450 Setup and Operation Screens Manual
64
Tank Label
This value is a description field for the tank. Usually it is based on the name of the product in the tank. It
should be unique for each tank. It is not the description value associated with the product code assigned
to the tank. The system will not require that a label be assigned to configure the tank, but a data setup
warning will occur if one is not assigned.
Allowable entry: 20 characters maximum - should be unique across tanks.
Default: Blank
Product Code
Enter the alphanumeric code used by a point-of-sale terminal or other external device to identify the
product for inventory control purposes.
Allowable entry: 1 character (all ASCII characters in the set 20h to 7Eh)
Default: A single character based on tank number, e.g., 1 to 9 for tank numbers 1 to 9 or A to W for tank
numbers 10 to 32.
Probe
Select the identifier of the probe installed in this tank from the drop down list. A probe assignment to a
tank is one to one (i.e. Probe 1 assigned to Tank 1, Probe 2 assigned to Tank 2, etc.).
Allowable entry: Select this probe's identifier from the drop down list.
Default: 'Not Assigned'
Probe Offset
This offset is intended for installations in which the probe is not resting on the bottom of the tank. The
value you enter (the distance off bottom) is continually added to the product height, but only to the water
height when the water float exceeds a minimum level.
Allowable selections: -144 to +144 in. (-3657.6 to +3657.6 mm)
Default: 0
Full Volume (Capacity)
Enter the full volume of the tank (at 100% height).
Allowable entry: 0 to 264,172 gallons (0 to 999, 999 litres)
Default: 0
Diameter
Enter the inside diameter of the selected tank (for a linear tank, enter the inside tank height in place of the
tank's inside diameter). You can find this dimension on the Tank Chart.
Allowable entry: 0 to 390.0 inches (0 to 9906.0mm)
Default: 0
Tank Tilt
Enter the tank tilt (if any) as calculated following instructions in the TLS-4XX Site Prep manual. If the
probe is installed in the center of the tank, enter 0.00 U.S. units or 0.00 Metric.
Allowable entry: -20.00 to +20.00 inches (-508.0 to +508.0mm)
Default: 0.00

Table of Contents

Other manuals for Veeder-Root TLS-450

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-450 and is the answer not in the manual?

Veeder-Root TLS-450 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-450
CategoryMusic Mixer
LanguageEnglish

Related product manuals