TLS-450 Setup and Operation Screens Manual
77
CSLD Evap. Compensation
Evaporation Compensation should only be enabled on individual tanks which have exhibited evidence of
consistent, extreme vapor loss due to fuel evaporation, which interferes with normal CSLD leak detection
monitoring by causing false leak alarms.
Note: This selection field will be enabled only if Climate Factor is set to Extreme.
Allowable selections: Enabled, Disabled
Default: Disabled
Stage II Vapor Recovery
This selection will be enabled only if Climate Factor is set to Extreme and CSLD Evap. Compensation is
enabled.
Allowable selections: Enabled, Disabled
Default: Disabled