WAGO-I/O-SYSTEM 750 CoDeSys 2.3 Runtime Environment 115
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Figure 15: Creating a new communication channel (RS 232) 2
6. Enter the following communication parameters of the RS-232 interface:
• Baud rate: 115200 bit/sec
• Parity: Even
• Stop Bits: 1
• Motorolla Byteorder: No
• Flow Control: Off
7. Transfer the PLC programs by clicking on Online in the menu bar and
select Login.
8. Remember that the I/O-IPCs Run/Stop switch must be in the "Run" position.
9. Start the PLC program by clicking on Online in the menu bar and selecting
Run.