246 I/O Modules WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Output Process Image
Byte Destination
Offset
High Byte Low Byte
Description
0 D0 C
DALI command,
DSI dimming value
Control byte
1 D2 D1 Parameter 2 DALI Address
2 D4 D3 Command extension Parameter 1
18.2.5.12 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 119: EnOcean Radio Receiver 750-642
Input Process Image
Byte Destination
Offset
High Byte Low Byte
Description
0 D0 S Data byte Status byte
1 D2 D1 Data bytes
Output Process Image
Byte Destination
Offset
High Byte Low Byte
Description
0 - C not used Control byte
1 - - not used
18.2.5.13 MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input
and Output Process Image (6 bytes of module data and 2 bytes of control/status).
The following table illustrates the Input and Output Process Image, which have 4
words mapped into each image. Word alignment is applied.
Table 120: MP Bus Master Module 750-643
Input and Output Process Image
Byte Destination
Offset
High Byte Low Byte
Description
0 C1/S1 C0/S0
extended
Control/
Status byte
Control/status
byte
1 D1 D0
2 D3 D2
3 D5 D4
Data bytes