Pos: 65 /Serie 758 (Funk, IPC und PFC)/Anhang/Anhang 7 58-87x WagoConfig ToolLIB_lib @ 12\mod_133853 9824410_21.doc @ 95800 @ 23 @ 1
19.1 WAGOConfigToolLIB.lib
With the function block of the CoDeSys "WAGOConfigToolLIB.lib" library,,
configure and parameterize the I/O-IPC like with the WBM and "IPC
Configuration Tool". You need the calls from the next Section. These have no
effect on the run time of the tasks because the functions are called asynchronsly.
configToolFB
bDone
bBusy
stResultString
iFbResult
iConfigToolResult
stConfigToolErrorString
bEnable
stCallString
Figure 118: Graphical representation of the "ConfigTool" function block
Table 127: "ConfigTool" function block
Parameter Name Data Type Description
bEnable BOOL The function block starts processing when the
input registers an ascending edge.
Input
stCallString STRING
(150)
Enter a call like in the Linux consol. An
overview of the calls is available in section
"Calls for the WAGOConfigToolLIB.lib
Library" .
bDone BOOL Indicates whether the function block is executed
fully or after canceled after reporting an error
code.
bBusy BOOL The function block processes a call.
Output
stResultString STRING
(80)
Return value displayed on the Linux console.
iFbResult INT The return values have the following meaning:
0: No error
1: Invalid input parameter, e.g. an
empty string at stCallString
2: Error at implementation of the
function block
3: Unknown Configtool
4: The Configtool result string is too large
for the function block return parameter
stResultString
iConfigToolResult INT The value corresponds directly to the Configtool
result parameter.
Output
stConfigToolError
String
STRING
(150)
This parameter displays the error description if
the call "wConfigToolResult" returns a value
0.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO WAGO-I/O-IPC-C6 and is the answer not in the manual?

WAGO WAGO-I/O-IPC-C6 Specifications

General IconGeneral
BrandWAGO
ModelWAGO-I/O-IPC-C6
CategoryI/O Systems
LanguageEnglish

Related product manuals