136 PROFIBUS Master in CoDeSys 2.3 WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
2. To select one (or several) PROFIBUS slaves, right click on the I/O-IPC
(WAGO-FB-DPM) and select "Append Subelement". In this example, the
750-343 (FW:08) was selected as the slave. Note that the firmware version
of the slave must match the selected GSD file.
Figure 61: Append PROFIBUS Slaves
GSD file
The GSD files for current WAGO-I/O-SYSTEM components are integrated in the
target files for the WAGO 758-875-000-111 I/O-IPC. The accompanying GSD
files must be used when connecting non-WAGO devices. To do this, click on
Extras > Add configuration file in the menu bar.