WAGO-I/O-SYSTEM 750 PROFIBUS Master in CoDeSys 2.3 163
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Station status 2:
Bit 1: Slave must be parameterized.
Bit 2: Slave provides diagnostic information until
this bit is zero again.
Bit 3: 1
Bit 4: Watchdog enabled.
Bit 5: Freeze command enabled.
Bit 6: Sync command enabled.
Bit 7: Reserved
Bit 8: Slave not designed.
Station status 3:
Bit 1: Reserved
Bit 2: Reserved
Bit 3: Reserved
Bit 4: Reserved
Bit 5: Reserved
Bit 6: Reserved
Bit 7: Reserved
Bit 8: Slave has more diagnostic data than it can
send.
Master Address:
This byte contains the address of the master that parameterized the slave. If a
slave was not parameterized, then the value is 255.
Ext_Diag_Data:
This is an extended diagnostic buffer. The values are defined in the manual of the
slave station or can be read in the PROFIBUS specification.