272 Appendix WAGO-I/O-SYSTEM 750
758-874/000-131 WAGO-I/O-IPC-C6
Manual
Version 1.0.0
Table 142: Description of the configuration scripts for " General SNMP information parameters "
Parameter Status Call Output/Input Validity
IP Address of a
Trap Receiver
read
get_snmp_data
v1-v2c-trap-receiver-
address <number>
Specifies the IP address of
the trap receiver, to which
the I/O-IPC should send the
v1 or v2 traps.
The <number> parameter
serves to enable
consecutive reading of the
related data from the
individually configured trap
receiver for a short period
of time (without interim
changing of the data). This
is a running number that is
not connected to the data. If
the number is not included,
the data of the first receiver
are read.
Community
Name
read
get_snmp_data
v1-v2c-trap-receiver-
community-name
<number>
Specifies the community
name that the SNMP agent
of the IPC sends in the Trap
Header.
Parameter <number>, see
section “IP Address of a
Trap Receiver”.
Trap Version read
get_snmp_data
v1-v2c-trap-receiver-
version <number>
Specifies the SNMP
version ("v1" or "v2c") via
which the SNMP agent
sends the traps to the
associated trap receiver
address.
Parameter <number>, see
section “IP Address of a
Trap Receiver”.
immediate
Creating/
deleting a trap
receiver
write
config_snmp
v1-v2c-trap-receiver-
edit=<value1>
v1-v2c-trap-receiver-
address=<value2>
v1-v2c-trap-receiver-
community-
name=<value3>
v1-v2c-trap-receiver-
version=<value4>
Create a new trap receiver
(value1=add) or delete an
already configured trap
receiver (value1=delete).
Additional parameters:
<value2> = IP address
(number.number.number.
number), to which the IPC
should send the traps.
<value3>: community
string (string), which the
IPC enters into the trap
header.
<value4>: SNMP version,
via which the traps are sent
(v1 or v2c).
Note:
When deleting a trap
receiver, all parameters
must also be entered, as this
is the only means to
uniquely identify the data
set.
after restart