EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startup Procedure and Test Run
4
4.6 Keypad Operation
YASKAWA SIEPC71061705H GA700 Series Technical Manual 163
7. When you are done changing the value, push .
The parameter setting procedure is complete.
Save a Backup of Parameters
You can save a backup of the drive parameters to the keypad. The keypad can store parameter setting values for a
maximum of four drives in different storage areas. Backups of the parameter settings can save time when you set
parameters after you replace a drive. When you set up more than one drive, you can copy the parameter settings
from a drive that completed a test run to the other drives.
Note:
Stop the motor before you back up parameters.
The drive will not accept a Run command while it makes a backup.
The DriveWorksEZ PC software password is necessary to back up qx-xx [DriveWorksEZ Parameter] and rx-xx [DWEZ Connection
Parameter]. If you enter an incorrect password, the drive detects PWEr [DWEZ Password Missmatch].
1. Push [Home] to show the HOME screen.
Note:
When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
If [Home] is not shown on , push (Back) to show [Home] on .
2. Push (Menu).
3. Push or to select [Parameter Backup/Restore], then push .
4. Push or to select the items to back up, then push .
5. Push or to select [Backup (drive keypad)], then push .

Table of Contents

Related product manuals