Parameter List
11
11.5 b: Application
YASKAWA SIEPC71061705H GA700 Series Technical Manual 489
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b5-92
(0B92)
RUN
EZ Sleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZ Sleep Time] to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
682
b5-93
(0B93)
RUN
EZ Sleep Time
Sets the length of time that the output frequency or motor speed must be less than b5-92
[EZ Sleep Level] to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
683
b5-94
(0B94)
RUN
EZ Sleep Wake-up Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
683
b5-95
(0B95)
EZ Sleep Wake-up Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Absolute
1 : Setpoint Delta
0
(0, 1)
683
b5-96
(0B96)
RUN
EZ Sleep Wake-up Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
683
◆ b6: Dwell Function
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b6-01
(01B6)
Dwell Reference at Start
Sets the output frequency that the drive will hold momentarily when the motor starts.
0.0
(Determined by A1-02)
684
b6-02
(01B7)
Dwell Time at Start
Sets the length of time that the drive will hold the output frequency when the motor
starts.
0.0 s
(0.0 - 10.0 s)
684
b6-03
(01B8)
Dwell Reference at Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
0.0
(Determined by A1-02)
684
b6-04
(01B9)
Dwell Time at Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop
the motor.
0.0 s
(0.0 - 10.0 s)
684
◆ b7: Droop Control
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b7-01
(01CA)
RUN
Droop Control Gain
Sets the amount of deceleration when the torque reference is at 100% as a percentage of
E1-04 [Maximum Output Frequency].
0.0%
(0.0 - 100.0%)
685
b7-02
(01CB)
RUN
Droop Control Delay
Time
Sets the responsiveness of Droop control. Decrease this setting when drive response is
slow. Increase this setting when hunting or oscillation occur.
0.05 s
(0.03 - 2.00 s)
685
b7-03
(017E)
Droop Control Limit
Selection
Sets the Droop control limit function.
0 : Disabled
1 : Enabled
1
(0, 1)
685