EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12.8 H: Terminal Functions
846 YASKAWA SIEPC71061705H GA700 Series Technical Manual
MEMOBUS/Modbus Multi-Function AI1 to 3 Function Selection
Let the MFAI function be assigned to MEMOBUS/Modbus register 15C1 to 15C3 (Hex.) [Mbus Reg 15C1h
through 15C3h Input Function]. Use H3-40 to H3-42 [Mbus Reg 15C1h through 15C3h Input Function] to set the
function and use H3-43 [Mbus Reg Inputs FilterTime Const] to set the input filter.
Table 12.70 MEMOBUS Multi-Function AI Command Register
Register No.
(Hex.)
Name Range
*1
Parameter
15C1 Mbus Reg 15C1h Input Function -32767 to 32767 H3-40
15C2 Mbus Reg 15C2h Input Function -32767 to 32767 H3-41
15C3 Mbus Reg 15C3h Input Function -32767 to 32767 H3-42
*1 Set as 100% = 4096.
Figure 12.106 Functional Block Diagram for MEMOBUS Multi-Function AI Command 1
Note:
Refer to H3-xx MFAI Setting Values for the analog input setting values.
When you will not use the terminal, set H3-40 to H3-42 = F. The through mode function is not supported.
You cannot use H3-40 to H3-42 to set these MFAI terminals:
H3-xx Setting Value Function
0 Frequency Reference
1 Frequency Gain
2 Auxiliary Frequency Reference 1
3 Auxiliary Frequency Reference 2
30 DWEZ Analog Input 1
31 DWEZ Analog Input 2
32 DWEZ Analog Input 3
H3: MFAI Parameters
H3-01: Terminal A1 Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H3-01
(0410)
Terminal A1 Signal Level
Select
Sets the input signal level for MFAI terminal A1.
0
(0 - 3)
0 : 0-10V (Lower Limit at 0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
1 : -10 to +10V (Bipolar Reference)
The voltage signal is -10 Vdc to 10 Vdc. Signals of both positive and negative polarities are enabled. When the
drive uses this setting as the frequency reference, a Forward Run command will run the motor in reverse and a
Reverse Run command will run the motor forward. The gain and bias settings will cause the signal to be a
negative number.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level limit is 0%. The minimum input level is limited to
0%, so that a negative input signal due to gain and bias settings will be read as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level limit is 0%. The minimum input level is limited to
0%, so that a negative input signal due to gain and bias settings will be read as 0%.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals