Startup Procedure and Test Run
4
4.6 Keypad Operation
YASKAWA SIEPC71061705H GA700 Series Technical Manual 183
A - Drive Series
B - Maximum Applicable Motor Output (HD/ND)
C - Rated Output Current (HD/ND)
D - Drive software version
E - Serial number
Write Automatically Backed-up Parameters to the Drive
You can automatically back up parameters to the keypad connected to the drive and write those parameters to a
drive from the same drive series as specified by the settings of o3-06 [Auto Parameter Backup Selection] and o3-
07 [Auto Parameter Backup Interval].
Note:
Set o3-06 = 1 [Auto Parameter Backup Selection = Enabled] in each drive to which you will write the parameters.
This operation is not available when the parameters in the keypad and the parameters on the other drives are set to the same values.
1. Connect the keypad to the drive.
2. Push or to select [Yes], then push .
3. Push or to select [Yes], then push .
The keypad will show the End message when the write process is complete.