Parameter Details
12
12.3 b: Application
YASKAWA SIEPC71061705H GA700 Series Technical Manual 641
12.3 b: Application
b parameters set the following functions.
Frequency reference source/Run command source
Stopping method settings
DC Injection Braking
Speed Search
Timer Function
PID control
Dwell function
Droop control
Energy Savings Control
Zero Servo Control
b1: Operation Mode Selection
b1 parameters set the operation mode for the drive.
b1-01: Frequency Reference Selection 1
No.
(Hex.)
Name Description
Default
(Setting Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
1
(0 - 4)
Note:
Push on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency]
value, on the keypad will flash. Examine the setting for the frequency reference input and enter a value more than or equal to E1-
09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use and on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
Voltage Input
Refer to Table 12.22 to use a voltage signal input to one of the MFAI terminals.
Table 12.22 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to V for
voltage input.
-10 - +10 V H3-01 = 1
A2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to V for
voltage input.
-10 - +10 V H3-09 = 1
A3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to V for
voltage input.
Set DIP switch S4 to AI for
analog input.
-10 - +10 V H3-05 = 1
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV