Parameter List
11
11.5 b: Application
YASKAWA SIEPC71061705H GA700 Series Technical Manual 491
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b8-28
(0B8B)
Expert
Over Excitation Action
Selection
Sets the function for excitation operation.
0 : Disabled
1 : Enabled
0
(0, 1)
689
b8-29
(0B8C)
Energy Saving Priority
Selection
Sets the priority of drive response between changes to the load or Energy-saving
control. Enable this to prioritize energy-saving control. Disable this to prioritize
tracking related to fast load changes, and prevent motor stall.
0 : Priority: Drive Response
1 : Priority: Energy Savings
0
(0, 1)
689
b8-50
(0B0D)
Standby Mode Selection
Sets the Standby Mode function.
0 : Disabled
1 : Enabled
0
(0, 1)
689
b8-51
(0B01)
Standby Mode Wait
Time
Sets the delay time before turning off the electromagnetic contactor after the drive
stops.
600 s
(0 - 6000 s)
690
◆ b9: Zero Servo
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b9-01
(01DA)
Zero Servo Gain
Sets the responsiveness for the Zero Servo function.
5
(0 - 100)
691
b9-02
(01DB)
Zero Servo Completion
Window
Sets the range to trigger an output terminal set for “Zero Servo Complete” during Zero
Servo operation. Be sure to set the deviation from the Zero Servo start position.
10
(0 - 16383)
691