11.21 Defaults by Drive Model and Duty Rating ND/HD
602 YASKAWA SIEPC71061705H GA700 Series Technical Manual
11.21 Defaults by Drive Model and Duty Rating ND/HD
The values for the parameters in these tables depend on the values for parameters o2-04 and C6-01. Changing the
settings for o2-04 and C6-01 will change the default settings.
◆ Three-Phase 200 V Class
No.
*1
Name Unit Default
- Drive Model - 2004 2006 2010
C6-01
Normal / Heavy
Duty Selection
-
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 62 63 65
E2-11
(E4-11)
Motor Rated
Power
kW 0.4 0.75 0.75 1.1 1.5 2.2
b3-04
V/f Gain during
Speed Search
% 100 100 100 100 100 100
b3-06
Speed Estimation
Current Level 1
- 1 1 0.5 0.5 0.5 0.5
b3-08
Speed Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient Value
- 288.2 223.7 223.7 196.6 169.4 156.8
C5-17
(C5-37)
Motor Inertia kgm
2
0.0015 0.0028 0.0028 0.0068 0.0068 0.0088
C6-02
Carrier Frequency
Selection
- 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 1.9 3.3 3.3 4.9 6.2 8.5
E2-02
(E4-02)
Motor Rated Slip Hz 2.9 2.5 2.5 2.6 2.6 2.9
E2-03
(E4-03)
Motor No-Load
Current
A 1.2 1.8 1.8 2.3 2.8 3
E2-05
(E4-05)
Motor Line-to-
Line Resistance
Ω 9.842 5.156 5.156 3.577 1.997 1.601
E2-06
(E4-06)
Motor Leakage
Inductance
% 18.2 13.8 13.8 18.5 18.5 18.4
E2-10
(E4-10)
Motor Iron Loss W 14 26 26 38 53 77
E5-01
PM Motor Code
Selection
- 1202 1202 1203 1203 1205 1205
L2-02
Power Loss Ride
Through Time
s 0.1 0.1 0.2 0.2 0.3 0.3
L2-03
Minimum
Baseblock Time
s 0.2 0.3 0.3 0.4 0.4 0.5
L2-04
Powerloss V/f
Recovery Ramp
Time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190
L3-24
Motor Accel
Time @ Rated
Torque
s 0.178 0.142 0.142 0.142 0.166 0.145
L8-02
Overheat Alarm
Level
°C 115 115 115 115 115 115
L8-09
Output Ground
Fault Detection
- 1 1 1 1 1 1