EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network Communications
6
6.3 MEMOBUS/Modbus Communications
YASKAWA SIEPC71061705H GA700 Series Technical Manual 309
Minor Fault/
Alarm Code
(Hex.)
Name
0042 TrPC [IGBT Maintenance Time (90%)]
0043 LT-3 [SoftChargeBypassRelay MainteTime]
0044 LT-4 [IGBT Maintenance Time (50%)]
0045 boL [Braking Transistor Overload]
0049 dWAL [DriveWorksEZ Alarm]
004A dWA2 [DriveWorksEZ Alarm 2]
004B dWA3 [DriveWorksEZ Alarm 3]
Minor Fault/
Alarm Code
(Hex.)
Name
0081
EP24v [External Power 24V Supply]
0085
bAT [Keypad Battery Low Voltage]
0087
CP1 [Comparator 1 Limit Error]
0088
CP2 [Comparator 2 Limit Error]
0089
TiM [Keypad Time Not Set]
008A
bCE [Bluetooth Communication Error]
Error Codes
MEMOBUS/Modbus Communications Error Code List
Table 6.20 lists the MEMOBUS/Modbus communications error codes.
When an error occurs, remove the cause of the error and restart communications.
Table 6.20 MEMOBUS/Modbus Communications Error Codes
Error Code
(Hex.)
Name Cause
01 Function Code Error The PLC set a function code that was not 03, 08, or 10 (Hex.)
02 Register Number Error
The register number that is trying to access is not registered.
A starting number that was not 0001 or 0002 (Hex.) was set when broadcasting.
03 Bit Count Error
Read and write data quantities are more than the 1 to 16 range. (Command message data quantity is disabled.)
The data that was read from non-consecutive holding registers contained more than 120 bytes.
The data to be written to non-consecutive holding registers contained more than 60 bytes.
In the write mode, the number of bytes in the message is not the number of data × 2.
21 Data Setting Error
Writing control data or parameters made the settings go out of the permitted setting range.
A parameter setting error occurred when writing a parameter.
22 Write Mode Error
Tried to write a disabled parameter during run.
When there was a CPF06 [Control Circuit Error], the master tried to write a parameter other than one of these:
A1-00 [Language Selection]
A1-01 [Access Level Selection]
A1-02 [Control Method Selection]
A1-03 [Initialize Parameters]
A1-04 [Password]
A1-05 [Password Setting]
E1-03 [V/f Pattern Selection]
o2-04 [Drive Model (KVA) Selection]
Writes the read-only data.
23
DC Bus Undervoltage
Write Error
During Uv [DC Bus Undervoltage], a Uv write disabled parameter was written.
24
Error Writing Data During
Parameter Processing
Tried to write a parameter from the master during parameter processing on the drive side.
25
Writing into EEPROM
Disabled
Writing into EEPROM write is disabled, but EEPROM write was executed from MEMOBUS/Modbus communications. When
this error occurs, the keypad shows a message and the drive continues operation.
No Response from Slave
The slave ignores the command message from the master and will not send a response message in these
conditions:
When a communications error (overrun, framing, parity, CRC-16) is detected in the command message.
When the slave address in the command message and the slave address for the drive side do not agree (Use H5-
01 [Drive Node Address] to set the slave address of the drive)
When the time interval between the data of which the message is composed is longer than 24 bits
When the data length for the command message is not accurate

Table of Contents

Related product manuals