Specifications
10
10.5 Drive Specifications
YASKAWA SIEPC71061705H GA700 Series Technical Manual 437
10.5 Drive Specifications
Note:
To get the OLV, CLV, and AOLV specifications, do Rotational Auto-Tuning.
To get the longest product life, install the drive in an environment that meets the necessary specifications.
Table 10.9 Control Characteristics
Item Specification
Control Methods
V/f Control
V/f Control with Encoder
Open Loop Vector
Closed Loop Vector
Advanced Open Loop Vector
PM Open Loop Vector
PM Advanced Open Loop Vector
PM Closed Loop Vector
EZ Vector Control
Frequency Control
Range
AOLVand EZOLV: 0.01 Hz to 120 Hz
CL-V/f, CLV, AOLV/PM, and CLV/PM: 0.01 Hz to 400 Hz
V/f, OLV, and OLV/PM: 0.01 Hz to 590 Hz
Frequency Accuracy
(Temperature
Fluctuation)
Digital inputs: ±0.01% of the maximum output frequency (-10 °C to +40 °C (14 °F to 104 °F))
Analog inputs: ±0.1% of the maximum output frequency (25 °C ±10 °C (77 °F ±18 °F))
Frequency Setting
Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency (11-bit signed)
Output Frequency
Resolution
0.001 Hz
Frequency Setting
Signal
Main speed frequency reference: -10 Vdc to +10 Vdc (20 kΩ), 0 Vdc to 10 Vdc (20 kΩ), 4 mA to 20 mA (250 Ω), 0 mA to 20 mA (250 Ω)
Main speed reference: Pulse train input (maximum 32 kHz)
Starting Torque
V/f: 150%/3 Hz
CL-V/f: 150%/3 Hz
OLV: 200%/0.3 Hz
CLV: 200%/0 min
-1
(r/min)
AOLV: 200%/0.3 Hz
OLV/PM: 100%/5% speed
AOLV/PM: 200%/0 min
-1
(r/min)
CLV/PM: 200%/0 min
-1
(r/min)
EZOLV: 100%/1% speed
Note:
Correctly select the drive and motor capacity for this starting torque in these control methods:
OLV
CLV
AOLV
AOLV/PM
CLV/PM
Set n8-57 = 1 [HFI Overlap Selection = Enabled] for this starting torque in AOLV/PM. When you use a non-Yaskawa PM motor, do Rotational
Auto-Tuning.
Speed Control Range
V/f: 1:40
CL-V/f: 1:40
OLV: 1:200
CLV: 1:1500
AOLV: 1:200
OLV/PM: 1:20
AOLV/PM: 1:100
CLV/PM: 1:1500
EZOLV: 1:100
Note:
Set n8-57 = 1 [HFI Overlap Selection = Enabled] for this Speed Control Range in AOLV/PM. When you use a non-Yaskawa PM motor, do
Rotational Auto-Tuning.
Speed control range of 1:100 for AOLV/PM is Instantaneous operation range. Correctly select the drive and motor capacity for continuous operation.
Zero Speed Control
Possible in these control methods:
CLV
AOLV/PM
CLV/PM