EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.10 Troubleshooting Without Fault Display
374 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Causes Possible Solutions
You entered an incorrect password in A1-04 [Password]. Enter the correct password to A1-04 again.
If you forgot the password, set the password again with A1-04 and A1-05 [Password Setting].
Note:
If you set the password, you cannot change these parameters until the password aligns:
A1-01 [Access Level Selection]
A1-02 [Control Method Selection]
A1-03 [Initialize Parameters]
A1-06 [Application Preset]
A1-07 [DriveWorksEZ Function Selection]
A2-01 to A2-32 [User Parameter 1 to User Parameter 32]
The drive detected Uv [Undervoltage]. View U1-07 [DC Bus Voltage] to see the power supply voltage.
Examine the main circuit wiring.
The Motor Does Not Rotate After Entering Run Command
Causes Possible Solutions
The drive is not in Drive Mode. 1. Make sure that the keypad shows [Rdy].
2. If the keypad does not show [Rdy], go back to the Home screen.
The drive stopped, was pushed, and changed the Run command
source to the keypad.
Do one of these two:
Push .
Re-energize the drive.
Note:
Set o2-01 = 0 [LO/RE Key Function Selection = Disabled] to prevent changing the Run
command source with .
Auto-Tuning completed. Go back to the Home screen on the keypad.
Note:
When Auto-Tuning completes, the drive changes to Programming Mode. The drive will not
accept a Run command unless the drive is in Drive Mode.
The drive received a fast stop command. Turn off the fast stop input signal.
The settings for the source that supplies the Run command are incorrect. Set b1-02 [Run Command Selection 1] correctly.
The frequency reference source is set incorrectly. Set b1-01 [Frequency Reference Selection 1] correctly.
There is defective wiring in the control circuit terminals. Correctly wire the drive control circuit terminals.
View U1-10 [Input Terminal Status] for input terminal status.
The settings for voltage input and current input of the master frequency
reference are incorrect.
Examine these analog input terminal signal level settings:
Terminal A1: DIP switch S1-1 and H3-01 [Terminal A1 Signal Level Select]
Terminal A2: DIP switch S1-2 and H3-09 [Terminal A2 Signal Level Select]
Terminal A3: DIP switch S4, S1-3 and H3-05 [Terminal A3 Signal Level Select]
The selection for the sinking/sourcing mode and the internal/external power
supply is incorrect.
For sinking mode, close the circuit between terminals SC-SP with a wire jumper.
For sourcing mode, close the circuit between terminals SC-SN with a wire jumper.
For external power supply, remove the wire jumper.
The frequency reference is too low. View U1-01 [Freq Reference].
Increase the frequency reference to a value higher than E1-09 [Minimum Output Frequency].
The MFAI setting is incorrect. Make sure that the functions set to the MFAI are correct. The frequency reference is 0 when
H3-02, H3-10, H3-06 = 1 [MFAI Function Select = Frequency Gain] and voltage (current) is
not input.
View U1-13 to U1-15 [Terminal A1, A2, A3 Input Voltage] to see if the analog input values set
to terminals A1, A2, and A3 are applicable.
was pushed.
Turn the Run command OFF then ON from an external input.
Note:
When you push during operation, the drive will ramp to stop. Set o2-02 = 0 [STOP
Key Function Selection = Disabled] to disable the function.
The 2-wire sequence and 3-wire sequence are set incorrectly. Set one of the parameters H1-03 to H1-08 [Terminals S3 to S8 Function Select] to 0 [3-Wire
Sequence] to enable the 3-wire sequence.
If a 2-wire sequence is necessary, make sure that H1-03 to H1-08 0.

Table of Contents

Related product manuals