Startup Procedure and Test Run
4
4.7 Automatic Parameter Settings Optimized for Specific Applications (Application Presets)
YASKAWA SIEPC71061705H GA700 Series Technical Manual 185
7. Push or to change the value, then push .
The parameter setting procedure is complete.
Note:
For hoist applications, make sure that you do Auto-Tuning after you set A1-06.
You cannot change the value set in A1-06. To select an application preset, first set A1-03 = 2220 to initialize parameters and then make
a selection to A1-06. If initializing all parameters will cause a problem, it is not necessary to change settings.
When the drive changes to the A1-06 setting, it will also reset the parameters automatically registered to A2-17 to A2-32 [User
Parameters 17 to 32] when A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms].