6.3 MEMOBUS/Modbus Communications
292 YASKAWA SIEPC71061705H GA700 Series Technical Manual
Register No.
(Hex.)
Description
3004
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at energize: 0000
Set the hour and the minute in HHMM format.
HH: 00 to 23 (decimal)
MM: 00 to 59 (decimal)
3005
Year and Day Setting
Setting range: 1600 to 9906 (decimal), the default value at energize: 1600
Sets the year and the day of the week in YYDW format.
YY: the last two digits of the year from 16 to 99 (decimal)
DW: the day of the week
Sunday: 00
Monday: 01
Tuesday: 02
Wednesday: 03
Thursday: 04
Friday: 05
Saturday: 06
3006
Date Setting
Setting range: 101 to 1231 (decimal), the default value at energize: 101
Sets the month and the date in MMDD format.
MM: 01 to 12 (decimal)
DD: 01 to 31 (decimal)
3007
Set the Date Information
Setting range: 0 to 8 (decimal), the default value at energize: 8
Sets the values specified in 3004H to 3006H as the date and time.
Command Data: 1
Response Data: 0 (normal), 8 (fault)
Monitor Data