Network Communications
6
6.3 MEMOBUS/Modbus Communications
YASKAWA SIEPC71061705H GA700 Series Technical Manual 305
Register No.
(Hex.)
Description
00E5
Minor Fault Description 9
bit 0 EP24v [External Power 24V Supply]
bit 1 - 3 Reserved
bit 4 bAT [Keypad Battery Low Voltage]
bit 5 Reserved
bit 6 CP1 [Comparator 1 Limit Fault]
bit 7 CP2 [Comparator 2 Limit Fault]
bit 8 TiM [Keypad Time Not Set]
bit 9 bCE [Bluetooth Communication Error]
bit A - F Reserved
00E6 - 00E9 Reserved
00EA
Fault Description 11
bit 0 TiM [Keypad Time Not Set]
bit 1 bAT [Keypad Battery Low Voltage]
bit 2- D Reserved
bit E SCF [Safety Circuit Fault]
bit F Reserved
00EB - 00ED Reserved
00EE
Fault Description 12
bit 0 - 2 Reserved
bit 3 CP1 [Comparator 1 Limit Fault]
bit 4 CP2 [Comparator 2 Limit Fault]
bit 5 bCE [Bluetooth Communication Fault]
bit 6 - F Reserved
00EF - 00FA Reserved
00FB
Output current
Note:
The unit of display is different for different models.
2004 to 2042, 4002 to 4023: 0.01 A
2056 to 2415, 4031 to 4675: 0.1 A
Broadcast Messages