Troubleshooting
7
7.4 Fault
YASKAWA SIEPC71061705H GA700 Series Technical Manual 345
Code Name Causes Possible Solutions
PF Input Phase Loss
There is a phase loss in the drive input power. Correct errors with the wiring for main circuit drive input power.
There is loose wiring in the drive input power
terminals.
Tighten the terminal screws to the correct tightening torque.
The drive input power voltage is changing too
much.
• Examine the input power for problems.
• Make the drive input power stable.
• If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
There is unsatisfactory balance between voltage
phases.
• Examine the input power for problems.
• Make the drive input power stable.
• Set L8-05 = 0 [Input Phase Loss Protection Sel = Disabled].
The main circuit capacitors have become
unserviceable.
• Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance]. If U4-05 is more than 90%, replace
the control board or the drive. For information about replacing
the control board, contact Yaskawa or your nearest sales
representative.
• If drive input power is correct and the fault stays, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
Note:
• The drive detects this error if the DC bus voltage changes irregularly without regeneration.
• Do a Fault Reset to clear the fault.
• Use L8-05 to enable and disable PF detection.
Code Name Causes Possible Solutions
PGo Encoder (PG) Feedback Loss
The encoder cable is disconnected or wired
incorrectly.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
The encoder is not receiving power. Examine the encoder power supply.
The holding brake is stopping the motor. Release the holding brake.
Note:
• The drive detects this error if it does not receive the speed detection pulse signal from the encoder in the detection time set in F1-14 [Encoder Open-Circuit Detect Time].
• Do a Fault Reset to clear the fault.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in F1-02 [PG Open Circuit Detection Select].
Code Name Causes Possible Solutions
PGoH Encoder (PG) Hardware Fault
The encoder cable is disconnected. Connect any disconnected wires in the encoder cable.
Note:
• Do a Fault Reset to clear the fault.
• Parameter F1-20 [Encoder 1 PCB Disconnect Detect] or F1-36 [Encoder 2 PCB Disconnect Detect] enables and disables PGoH detection.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in F1-02 [PG Open Circuit Detection Select].
Code Name Causes Possible Solutions
rF Braking Resistor Fault
The resistance of the dynamic braking option that is
connected to the drive is too low.
Use a dynamic braking option that fits the model and duty rating
of the drive.
A regenerative converter, regenerative unit, or
braking unit is connected to the drive.
Set L8-55 = 0 [Internal DB TransistorProtection = Disable].
Note:
Do a Fault Reset to clear the fault.
Code Name Causes Possible Solutions
rH Braking Resistor Overheat
The deceleration time is too short and excessive
regenerative energy is flowing back into the drive.
• Check the load level, deceleration time, and speed.
• Decrease the load.
• Increase the values set in C1-02, C1-04, C1-06, or C1-08
[Deceleration Times].
• Use a dynamic braking option that lets you use more power.
The duty cycle is too high. Examine the duty cycle.
Note:
When L8-01 = 1 [3% ERF DB Resistor Protection =
Enabled], the maximum braking duty cycle is 3%.
The braking load is too heavy. • Calculate the braking load and braking power again, and
decrease the braking load.
• Use a braking resistor that improves braking power.
The braking resistor is not sufficient. Use the braking resistor specifications to select a sufficient
braking resistor.
Note:
• The drive detects this error if the braking resistor overheat protective function is active.
• The magnitude of the braking load causes the braking resistor overheat alarm, NOT the surface temperature. If the duty cycle is higher than the braking resistor rating, the
drive will show the alarm.
• Do a Fault Reset to clear the fault.
• Parameter L8-01 enables and disables rH detection.