Specifications
10
10.5 Drive Specifications
YASKAWA SIEPC71061705H GA700 Series Technical Manual 439
Item Specification
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
• There is a low-resistance ground fault for the motor cable or terminal block
• Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Table 10.11 Environment
Item Specification
Area of Use
Indoors
Power supply
Overvoltage Category III
Ambient
Temperature Setting
IP20/UL Open Type: -10°C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
• You can use IP20/UL Open Type drives at a maximum of 60 °C (140 °F) when you derate the output current.
• You can use IP20/UL Type 1 drives at a maximum of 50 °C (122 °F) when you derate the output current.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
Altitude
1000 m (3281 ft) Maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the neutral point on the power supply.
Contact Yaskawa or your nearest sales representative if you will not ground the neutral point.
Vibration
• 10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
• 20 Hz to 55 Hz:
2004 to 2211, 4002 to 4168: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
2257 to 2415, 4208 to 4675: 0.2 G (2.0 m/s
2
, 6.56 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient airflow to cool the drive.
Table 10.12 Standard
Item
Specification
Harmonized Standard
• UL61800-5-1
• EN61800-3
• IEC/EN61800-5-1
• Two Safe Disable inputs and one EDM output according to EN ISO 13849-1:2015 (PL e (Cat.III)), IEC/EN61508 SIL3
Enclosure Protection
Design
IP20/UL Open Type
IP20/UL Type 1
Note:
To change an IP20/UL Open Type drive to an IP20/UL Type 1 drive, install a UL Type 1 kit.