11.9 F: Options
520 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-70
(078A)
PZD1 Read (Status
Word)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD1 (PPO
input). PZD1 (PPO input) functions as the ZSW when F7-70 = 0.
0 797
F7-71
(078B)
PZD2 Read (Output
Frequency)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO
input). PZD2 (PPO input) functions as the HIW when F7-71 = 0.
0 797
F7-72
(078C)
PZD3 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO
input). A value of 0 will disable the PZD3 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 797
F7-73
(078D)
PZD4 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO
input). A value of 0 will disable the PZD4 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 797
F7-74
(078E)
PZD5 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO
input). A value of 0 will disable the PZD5 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 797
F7-75
(078F)
PZD6 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO
input). A value of 0 will disable the PZD6 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 798
F7-76
(0790)
PZD7 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO
input). A value of 0 will disable the PZD7 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 798
F7-77
(0791)
PZD8 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD8 (PPO
input). A value of 0 will disable the PZD8 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 798
F7-78
(0792)
PZD9 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD9 (PPO
input). A value of 0 will disable the PZD9 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 798
F7-79
(0793)
PZD10 Read
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD10
(PPO input). A value of 0 will disable the PZD10 (PPO input) load operation from the
MEMOBUS/Modbus register.
0 798