Parameter Details
12
12.4 C: Tuning
YASKAWA SIEPC71061705H GA700 Series Technical Manual 703
C4-03: Torque Compensation @ FWD Start
No.
(Hex.)
Name Description
Default
(Range)
C4-03
(0217)
Torque Compensation @
FWD Start
Set the amount of torque reference for forward start as a percentage of the motor rated torque.
0.0%
(0.0 - 200.0%)
The torque compensation function is performed using the time constant set in C4-05 [Torque Compensation
Time].
This is available only when you start the motor with the forward command. Set this parameter to 0.0 to disable
this function.
C4-04: Torque Compensation @ REV Start
No.
(Hex.)
Name Description
Default
(Range)
C4-04
(0218)
Torque Compensation @
REV Start
Sets the amount of torque reference for reverse start as a percentage of the motor rated torque.
0.0%
(-200.0 - 0.0%)
The drive uses the time constant set in C4-05 [Torque Compensation Time] to do the torque compensation
function.
This is available only when you start the motor with the reverse Run command.
C4-05: Torque Compensation Time
No.
(Hex.)
Name Description
Default
(Range)
C4-05
(0219)
Torque Compensation Time
Sets the starting torque constant to use with C4-03 and C4-04 [Torque Compensation @ FWD/
REV Start].
10 ms
(0 - 200 ms)
C4-06: Motor 2 Torque Comp Delay Time
No.
(Hex.)
Name Description
Default
(Range)
C4-06
(021A)
Motor 2 Torque Comp
Delay Time
Sets the value if ov [Overvoltage] occurs with sudden changes in the load, at the end of
acceleration, or at the start of deceleration.
150 ms
(0 - 10000 ms)
Sets the time constant used during Speed Search or during regenerative operation when ov occurs.
Adjust this parameter in the following circumstances.
Gradually reduce the setting in 10 ms increments and check the performance to improve motor torque speed
response when ov occurs.
Note:
Ensure that C4-06 C4-02 [Torque Compensation Delay Time].
Increase the setting value of n2-03 [Automatic Freq Regulator Time 2] proportional to C4-06.
C4-07: Motor 2 Torque Compensation Gain
No.
(Hex.)
Name Description
Default
(Range)
C4-07
(0341)
RUN
Motor 2 Torque
Compensation Gain
Sets the gain for motor 2 torque compensation function when using the Motor Switch function.
1.00
(0.00 - 2.50)
In V/f Control or CL-V/f Control, adjust the value in 0.05 unit increments for these conditions:
When torque is not sufficient during low-speed operation of 10 Hz or less, increase the setting value
When there is vibration in the motor or when the motor hunts when operating the drive with a light load,
decrease the setting value
When you use a long motor cable, increase the setting.
Note:
Adjust C4-07 and make sure that the output current is not more than the drive rated current during low-speed operation.
When A1-02 = 2 [Open Loop Vector], usually it is not necessary to change this setting. If you change this parameter in that control
method, it can decrease the torque precision.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV