12.7 F: Options
784 YASKAWA SIEPC71061705H GA700 Series Technical Manual
0 : Always Detected
1 : Detected during RUN Only
F6-03: Comm External Fault (EF0) Select
No.
(Hex.)
Name Description
Default
(Range)
F6-03
(03A4)
Comm External Fault (EF0)
Select
Sets the method to stop the motor or let the motor continue operating when the drive detects an
EF0 [Option Card External Fault].
1
(0 - 3)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and
MB-MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC
turns OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-
MC turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows EF0 and the drive continues operation.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
F6-04: bUS Error Detection Time
No.
(Hex.)
Name Description
Default
(Range)
F6-04
(03A5)
bUS Error Detection Time
Sets the delay time for the drive to detect bUS [Option Communication Error].
2.0 s
(0.0 - 5.0 s)
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
F6-06: Torque Reference/Limit by Comm
No.
(Hex.)
Name Description
Default
(Range)
F6-06
(03A7)
Torque Reference/Limit by
Comm
Sets the function that enables and disables the torque reference and torque limit received from the
communication option.
0
(0, 1)
0 : Disabled
1 : Enabled
F6-07: Multi-Step Ref @ NetRef/ComRef
No.
(Hex.)
Name Description
Default
(Range)
F6-07
(03A8)
Multi-Step Ref @ NetRef/
ComRef
Sets the function that enables and disables the multi-step speed reference when the frequency
reference source is NetRef or ComRef (communication option card or MEMOBUS/Modbus
communications).
0
(0, 1)
0 : Disable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed to 16-
step speed references) and the Jog Frequency Reference (JOG command) are disabled.
1 : Enable Multi-Step References
When NetRef or ComRef are the frequency reference source, the multi-step speed reference (2-step speed through
16-step speed references) and the Jog Frequency Reference (JOG command) are enabled, and you can change the
frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV