12.7 F: Options
796 YASKAWA SIEPC71061705H GA700 Series Technical Manual
■ F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
(Hex.)
Name Description
Default
(Range)
F7-33 to F7-42
(0375 - 037E)
Dynamic In Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from
the MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The
drive returns the default register value for the option card when the MEMOBUS/Modbus address
is 0 and the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set
F7-33 to F7-37 to configurable inputs 1-5.
0
■ F7-60: PZD1 Write (Control Word)
No.
(Hex.)
Name Description
Default
(Range)
F7-60
(0780)
PZD1 Write (Control Word)
When you use a Profibus option, set the MEMOBUS/Modbus address for PZD1 (PPO output).
PZD1 (PPO output) functions as the STW when F7-60 = 0 to 2.
0
■ F7-61: PZD2 Write (Frequency Reference)
No.
(Hex.)
Name Description
Default
(Range)
F7-61
(0781)
PZD2 Write (Frequency
Reference)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO output).
PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.
0
■ F7-62: PZD3 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-62
(0782)
PZD3 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO output). A
value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
■ F7-63: PZD4 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-63
(0783)
PZD4 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO output). A
value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
■ F7-64: PZD5 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-64
(0784)
PZD5 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO output). A
value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
■ F7-65: PZD6 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-65
(0785)
PZD6 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO output). A
value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the MEMOBUS/Modbus
register.
0
■ F7-66: PZD7 Write
No.
(Hex.)
Name Description
Default
(Range)
F7-66
(0786)
PZD7 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO output). A
value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the MEMOBUS/Modbus
register.
0