EasyManua.ls Logo

YASKAWA GA700 Series

YASKAWA GA700 Series
1021 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
12
12.8 H: Terminal Functions
YASKAWA SIEPC71061705H GA700 Series Technical Manual 805
6: Jog Reference Selection
Setting Value Function Description
6 Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG Frequency Reference (JOG
command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
7: Accel/Decel Time Selection 1
Setting Value Function Description
7 Accel/Decel Time Selection
1
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/Deceleration Time 2 [C1-03, C1-04].
Note:
Refer to C1: Accel & Decel Time on page 692 for more information.
8: Baseblock Command (N.O.)
Setting Value Function Description
8 Baseblock Command (N.
O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
WARNING! Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
Figure 12.82 Baseblock Command Time Chart
ON : Baseblock (drive output stop)
OFF : Normal operation
9: Baseblock Command (N.C.)
Setting Value Function Description
9 Baseblock Command (N.
C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the
drive will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
WARNING! Sudden Movement Hazard. When you use a mechanical holding brake with the drive in a lifting application, you
must close the brake if an input terminal triggers the Baseblock command to stop drive output. If you enter the baseblock
command, the motor will suddenly coast and the load will slip, which can cause serious injury or death.
A: Accel/Decel Ramp Hold
Setting Value Function Description
A Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Related product manuals